XXV SEMINÁRIO NACIONAL DE
PRODUÇÃO E TRANSMISSÃO
DE ENERGIA ELÉTRICA


BELO HORIZONTE - MG

10 A 13

NOVEMBRO/2019
2019 - EXPOMINAS
Grupo: GTM
Tema: Técnicas de Ensaio, Medição, Calibração, Monitoramento e Diagnóstico:
Título: Sistema de Medição para Ensaios de Perfuração Em Isoladores
Autores: Márcio Thelio Fernandes da Silva(1); Ighor Souza dos Santos(2); Luiz Carlos de Azevedo(1); Valdir Remilson Santos(1); Marcus Vinicius Barros Lopes(1)
Instituições: CEPEL(1); PUC-Rio(2)
Resumo: Quantificar a amplitude de um impulso de perfuração, com todas as garantias metrológicas, não é uma tarefa trivial, por se tratar de um sinal impulsivo com centenas de kV e frentes rápidas entre 100 ns e 200 ns. Embora o ensaio de perfuração seja normatizado pela IEC 61211 ainda não existem na maioria dos Institutos Nacionais de Metrologia (INM), inclusive no Brasil, padrões para rastrear sistemas de medição utilizados nesses ensaios. Além disso, divisores de tensão com alto desempenho dinâmico para essa aplicação não estão disponíveis comercialmente e são objetos de pesquisa dos próprios INM e ou instituições de P&D+I.