Warning: session_start() [function.session-start]: Cannot send session cookie - headers already sent by (output started at /home/storage5/e/7d/18/bvr1/public_html/snptee/xxvsnptee/trabalhos/GTM/4176.php:2) in /home/storage5/e/7d/18/bvr1/public_html/snptee/xxvsnptee/redirect.php on line 2

Warning: session_start() [function.session-start]: Cannot send session cache limiter - headers already sent (output started at /home/storage5/e/7d/18/bvr1/public_html/snptee/xxvsnptee/trabalhos/GTM/4176.php:2) in /home/storage5/e/7d/18/bvr1/public_html/snptee/xxvsnptee/redirect.php on line 2

XXV SEMINÁRIO NACIONAL DE
PRODUÇÃO E TRANSMISSÃO
DE ENERGIA ELÉTRICA


BELO HORIZONTE - MG

10 A 13

NOVEMBRO/2019
2019 - EXPOMINAS
Grupo: GTM
Tema: Técnicas de Ensaio, Medição, Calibração, Monitoramento e Diagnóstico:
Título: Uso de Metanol e Etanol no Diagnóstico de Falhas Térmicas Envolvendo Papel Kraft Isolante
Autores: Helena Maria Wilhelm(1); Paulo O. Fernandes(1); Geovana Carolina dos Santos(1); Maria Letícia Gomes dos Santos(1); Thatiane Tamyris Kuczera Pereira(1); Daniel da Conceição Aroucha Filho(2); Marcelo Luiz de Carvalho Ribeiro(2); Arley de Paula Mar(2); Pedro Jose dos Santos Junior(2)
Instituições: VEGOOR(1); GERA MARANHÃO(2)
Resumo: Falha térmica envolvendo papel isolante foi simulada em laboratório em dispositivo específico para esta finalidade. O dispositivo de envelhecimento acelerado (patente requerida) permite aquecer o papel em altas temperaturas (até 1000 0C) mantendo o óleo isolante em baixa temperatura. O papel foi enrolado na resistência imersa em óleo e aquecida em diferentes temperaturas e tempos. Houve carbonização do papel nas camadas próximas da resistência. A quantidade e o tipo de gases encontrados no óleo indicaram a ocorrência da falha térmica simulada. Recomenda-se o uso da razão CO2/CO, da concentração de metanol e etanol no diagnóstico de falha envolvendo papel isolante.